Weidmuller Power Monitor
Brand: Weidmuller
Product Code: 1423550000
Availability:
Order In
Check Lead time
Typically 3-5 Days.
Please Contact Us for the exact availability and lead time.
$685.00 inc. GST
$622.73 + DeliveryTo calculate delivery cost, add this item to your cart and enter your shipping address at Checkout. Shipping FAQHave a question?
Weidmuller Power Monitor
Electrical parameters have to be measured and visualised to optimise your machines' and systems' energy needs. This is the only way in which an analysis can be carried out and, subsequently, savings made and an energy management system established. An easy-to-install solution is now available from Weidmüller. When implementing an energy management system according to ISO 50001, the Power Monitor is one of the modules necessary to meet the requirements of recording, displaying and analysing power flows.
Product Specifications
Measuring Current Input | |
Current-measuring channels | 3 |
Measuring accuracy for current | 0.5 % |
Rated current | 1 / 5 A |
Residual current measuring | |
Measuring Voltage Input | |
Four-wire system | Yes |
Measurement range, voltage L-L, AC | 0…500 V |
Measurement range, voltage L-N, AC | 0…250 V (1P3W), 0…289 V (3P4W) |
Measuring accuracy for voltage | 1 % |
Three-wire system | Yes |
Communication | |
Interface | RS485: Autobaud, 9.6 – 115.2 kbps (pluggable screw terminals) |
Protocol | Modbus RTU |
Technical Data | |
Standards | IEC 61010-1 |
Measurement range, voltage L-N, AC | 0…250 V (1P3W), 0…289 V (3P4W) |
Measurement range, voltage L-L, AC | 0…500 V |
Surge voltage category | II |
Supply voltage | 100…240 V AC, 100...300 V DC |
Three-wire system | Yes |
Four-wire system | Yes |
Sampling frequency 50/60 Hz | 1,024 kHz |
Measurement result per second | 100,000 |
Residual current measuring | No |
Measuring accuracy for voltage | 1 % |
Measuring accuracy for current | 0.5 % |
Measurement accuracy for active energy (kWh, …/5 A) | 1% for the calculated values |
Current-measuring channels | 3 |
Clock | Yes |
Voltage Quality Measurement | |
Positive, negative and zero system | Yes |
Brief interruptions | Yes |
Sequence-of-events recorder function | No |
Approvals | |
Approvals |
![]() ![]() |
ROHS | Conform |