Weidmuller Remote I/O Analog Output 4-channel Current/Voltage

Brand: Weidmuller

Product Code: 2453870000

Availability: Order In Check Lead time Typically 3-5 Days.
Please Contact Us for the exact availability and lead time.

474.58

$474.58 inc. GST

$431.44 + DeliveryTo calculate delivery cost, add this item to your cart and enter your shipping address at Checkout. Shipping FAQ

Qty

Ask about this productAsk about this product

UR20-4AO-UI-16-M-DIAG Remote I/O module, IP20, Analog signals, Output, 4-channel, Current/Voltage - Weidmuller

Product Specifications

Analogue Outputs  
Accuracy ±0,1 % FSR max., 0,05 % FSR typ.
Actuator connection 2-wire (automatic detection), Quadruple conductor
Cross-talk between the channels 0.001 % FSR
Individual channel diagnosis Yes
Max. error between T min. and T max. 220 ppm FSR
Module diagnosis Yes
Monotonicity Yes
Number
Output variable Voltage (0…5 V, 0…10 V, 1…5 V, 2…10 V, ±10 V, ±5 V), Current (0…20 mA or 4…20 mA)
Repeat accuracy < 1 mV eff.
Resolution 16 Bit
Response time 1 ms / 4 channels
Short-circuit-proof Yes
Temperature coefficient 20 ppm voltage / 31 ppm current measurement / °K
Type 1. U (0…5 V, 0…10 V, 1…5 V, 2…10 V, ±10 V), 2. I (0–20 mA or 4–20 mA)
load impedance current < 600 Ω
load impedance voltage > 1 kΩ (at > 50 °C ambient temperature, max. total sensor current = 25 mA)
Power Supply  
Current consumption from IIN (power segment of the field bus coupler), typ. 8 mA
Current consumption from IOUT (the respective power segment) 85 mA
Supply voltage 24 V DC +30 %/ -25 %, via the system bus
System Data  
Field bus protocol CANopen, DeviceNet, EtherCAT, EtherNet/IP, Modbus/TCP, PROFINET IRT, PROFIBUS DP-V1, POWERLINK
Galvanic isolation DC 500 V between current paths
Interface u-remote system bus
Module type Analogue output module
Process data 8 Byte
Transmission speed of system bus, max. 48 Mbit
Approvals  
Approvals ABS BURVER DNVGL LLOYDSREG RINA
ROHS Conform